需要disable optimized block access
protection /permit access with PUT/GET
Address | Step7 equivalent | JS Data type | Description |
---|---|---|---|
DB5,X0.1 |
DB5.DBX0.1 |
Boolean | Bit 1 of byte 0 of DB 5 |
DB23,B1 or DB23,BYTE1 |
DB23.DBB1 |
Number | Byte 1 (0-255) of DB 23 |
DB100,C2 or DB100,CHAR2 |
DB100.DBB2 |
String | Byte 2 of DB 100 as a Char |
DB42,I3 or DB42,INT3 |
DB42.DBW3 |
Number | Signed 16-bit number at byte 3 of DB 42 |
DB57,WORD4 |
DB57.DBW4 |
Number | Unsigned 16-bit number at byte 4 of DB 57 |
DB13,DI5 or DB13,DINT5 |
DB13.DBD5 |
Number | Signed 32-bit number at byte 5 of DB 13 |
DB19,DW6 or DB19,DWORD6 |
DB19.DBD6 |
Number | Unsigned 32-bit number at byte 6 of DB 19 |
DB21,R7 or DB21,REAL7 |
DB21.DBD7 |
Number | Floating point 32-bit number at byte 7 of DB 21 |
DB2,S7.10 * |
- | String | String of length 10 starting at byte 7 of DB 2 |
I1.0 or E1.0 |
I1.0 or E1.0 |
Boolean | Bit 0 of byte 1 of input area |
Q2.1 or A2.1 |
Q2.1 or A2.1 |
Boolean | Bit 1 of byte 2 of output area |
M3.2 |
M3.2 |
Boolean | Bit 2 of byte 3 of memory area |
IB4 or EB4 |
IB4 or EB4 |
Number | Byte 4 (0 -255) of input area |
QB5 or AB5 |
QB5 or AB5 |
Number | Byte 5 (0 -255) of output area |
MB6 |
MB6 |
Number | Byte 6 (0 -255) of memory area |
IC7 or EC7 |
IB7 or EB7 |
String | Byte 7 of input area as a Char |
QC8 or AC8 |
QB8 or AB8 |
String | Byte 8 of output area as a Char |
MC9 |
MB9 |
String | Byte 9 of memory area as a Char |
II10 or EI10 |
IW10 or EW10 |
Number | Signed 16-bit number at byte 10 of input area |
QI12 or AI12 |
QW12 or AW12 |
Number | Signed 16-bit number at byte 12 of output area |
MI14 |
MW14 |
Number | Signed 16-bit number at byte 14 of memory area |
IW16 or EW16 |
IW16 or EW16 |
Number | Unsigned 16-bit number at byte 16 of input area |
QW18 or AW18 |
QW18 or AW18 |
Number | Unsigned 16-bit number at byte 18 of output area |
MW20 |
MW20 |
Number | Unsigned 16-bit number at byte 20 of memory area |
IDI22 or EDI22 |
ID22 or ED22 |
Number | Signed 32-bit number at byte 22 of input area |
QDI24 or ADI24 |
QD24 or AD24 |
Number | Signed 32-bit number at byte 24 of output area |
MDI26 |
MD26 |
Number | Signed 32-bit number at byte 26 of memory area |
ID28 or ED28 |
ID28 or ED28 |
Number | Unsigned 32-bit number at byte 28 of input area |
QD30 or AD30 |
QD30 or AD30 |
Number | Unsigned 32-bit number at byte 30 of output area |
MD32 |
MD32 |
Number | Unsigned 32-bit number at byte 32 of memory area |
IR34 or ER34 |
IR34 or ER34 |
Number | Floating point 32-bit number at byte 34 of input area |
QR36 or AR36 |
QR36 or AR36 |
Number | Floating point 32-bit number at byte 36 of output area |
MR38 |
MR38 |
Number | Floating point 32-bit number at byte 38 of memory area |
DB1,DT0 |
- | Date** | A timestamp in the DATE_AND_TIME format |
DB1,DTZ10 |
- | Date** | A timestamp in the DATE_AND_TIME format, in UTC |
DB2,DTL2 |
- | Date** | A timestamp in the DTL format |
DB2,DTLZ12 |
- | Date** | A timestamp in the DTL format, in UTC |
DB57,RWORD4 |
DB57.DBW4 |
Number | Unsigned 16-bit number at byte 4 of DB 57, interpreted as Little-Endian |
DB13,RDI5 or DB13,RDINT5 |
DB13.DBD5 |
Number | Signed 32-bit number at byte 5 of DB 13, interpreted as Little-Endian |
MRW20 |
MW20 |
Number | Unsigned 16-bit number at byte 20 of memory area, interpreted as Little-Endian |
- *) Note that strings on the PLC uses 2 extra bytes at start for size/length of the string
- **) Note that javascript's
Date
are always represented in UTC. Please use other nodes like node-red-contrib-moment to properly handle type conversions